TREND AND APPLICATIONS OF ABSORPTION CHILLER

 

Sea Group

B.C. Chung - Century Corporation, Korea

 

1. INTRODUCTION

 

Since human being's desire for comfortable environment is instinctive, demand for HVAC increasingly grows as one's increases. Therefore propagation of air-conditioning facility is highly enlarged in countries which have been achieving economic growth. At present, most of the popular chillers as large tonnage of air conditioners are electrically driven. These electric chillers, which work perfectly under sufficient power supply, are causing a great deal of problems when the electric power condition is poor. In this area, the electric chiller is not proper to carry out varying cooling load according to the seasonal changes a peak load in some seasons and a partial load in other seasons. The electrically driven chiller have some problems something like this. In this case, the electric power condition can be improved by replacing the electric chiller system with those which use different types of energy, which is relatively sufficient compared with electricity. In general, when there is a peak load for air conditioning in a building, about 20% of the total electric power consumption is due to the air-conditioning system.  Furthermore, electric chillers consume 70% out of the 20%, which amounts to 14% of total electric power consumption. Therefore it is required to substitution these electric chillers to non-electric ones to cope with an electric power shortage. A representative of non-electric chiller is an absorption type. The absorption chiller consumes only 510% electric power compare with an electric chiller, as auxiliary power and power for control. The main energy can be used several kind of heat source, for instance gas fuel, liquid fuel, steam, hot water, solar heat, high temperature exhaust gas, etc. instead of electricity. About 1213% of the total electric power consumption in a building can be saved if an absorption type is adopted. Therefore if the absorption chillers are adopted on a nationwide scale, it is an effective and efficient solution to solve problems associated with an electric power shortage. Since any heat energy that has high temperature but has been wasted, and than if it can be used as a driving heat source of the absorption chiller, it is more useful energy saving application of the absorption chiller. The absorption chiller utilizes distilled water as a refrigerant not freon. Hence it is very friendly to the global environment.

 

 

2. ADVANTAGE OF ABSORPTION CHILLER

 

1) Electric power consumption is only 1/201/10 of a vapor compression type chiller.

 

The comparison for the electric power consumption is as follows in case a 170 usRT chilled installed. The electric power consumption is around 187 kWh when an electrically driven centrifugal chiller and a boiler are installed as a HVAC system. Here the centrifugal chiller consumes about 130 kWh and takes up nearly 70% of the electric power consumption of the entire air-conditioning system. On the contrary, if a direct-fired double effect absorption chiller installed, the power consumption of the entire air-conditioning system can be reduce to 70 kWh. In this case the direct-fired double effect absorption chiller consumes about 8 kWh, which is only 6.1% of the electric power consumption of the centrifugal chiller.

 

2) Contributes to prevention of environmental pollution by introducing non-freon refrigerant.

 

Centrifugal chillers mainly used for the cooling load of more than 100 usRT and they have used R123 as a refrigerant whose ODP(Ozen Deplection Potential) is 0.022 and GWP(Global Warming Potential) is 0.02. From several years ago, it is in the process of replacing R123 with R134a whose ODP is 0 and GWP is 0.29. But, because the GWP of R134a is very higher than R123's, R134a is not a complete alternative refrigerant. On the contrary, the absorption chiller utilizes distilled water as a refrigerant, and lithium bromide solution as a absorbent. The absorbent is also stable and unharmful to the human body. Hence the absorption type is very favorable to the environment.

 

3) The system is safe since it is operated under vacuum state.

 

Water serving as a refrigerant evaporates at 5, condenses at 40, and regenerates at 90 during operation of the fully vacuumed absorption chiller. This is meaning that the system maintains vacuum condition in operation. So, there is no chance for the system to experience physical damage of explosion.

 

4) Saving installation area

 

In case of heating and cooling are required, the direct fired absorption chiller heater system reduces required installation area by 40% when compared with a system composed of an electric centrifugal chiller and a boiler. Consequently, the absorption chiller heater system increases availability of the building.

 

5) Operating characteristics under a partial load are excellent.

 

The chillers are operated under a partial load rating between 50 and 70% for the most period of operation. And then, the absorption chiller has higher efficiency at partial load operation more than full load operation. It is also higher compare with the electrically driven centrifugal chiller. Thus absorption chiller system can save running cost to a great extent.

 

3. TREND OF ABSORPTION TYPE IN KOREA

 

The typical outdoor temperature in Korea is in the range of 28 38 in summer and 5 -20 in winter. Therefore energy consumption patterns are very much different from season to season like as shown in Fig. 1. The electric power consumption and the fuel oil consumption cross each other to the opposite direction in a period of 1 year. This requires facility which corresponds to the maximum consumption of both energy types. However the operating time under a peak load is relatively short. Accordingly the Korean government makes every effort to reduce these maximum points.

 

 

          Fig. 1. DEMAND PATTERNS OF LNG AND ELECTRICITY

 

1) The policy and circumstances of electric power in Korea.

The maximum electric power demand reached 41,007 MW in August, 2000. And then, the electric power consumption for air conditioning systems takes around 20% of the total power consumption under the peak load in Korea. And the amount of the power used for the air-conditioning is 8,073 MW which amounts to the power generated by the 8th nuclear power plants.(Total construction expense is approximately $9.2 billion.) The Korean government is in the process of considering and carrying various policies. Typical examples are as follows.

 

(1) Enhancing propagation of the absorption chiller and ice storge system.

(2) Enhancing propagation of high efficiency appliances.

(3) Enlarging the role of co-generation facility and emergency electric generators.

(4) Power late policy for demand management.

Among the above countermeasures, propagation of the absorption chiller is enlarged  through the policies as belows.

 

2) Policy and subsidy for augmenting propagation of absorption of chiller.

(1) Financing for the purchase of the facility.

(2) Applying discounted gas rates.

(3) Reduction and exemption from taxes.

(4) Discounting the installation cost for city gas piping.

(5) Mandatory installation of the gas-fired absorption chiller for new buildings.

(6) Restrictive policy for the types of fuel.

(7) Korea Electric Power Institute has started providing a loan, and renting the absorption chiller system.

 

 

4. NEW APPLICATIONS OF ABSORPTION CYCLE IN KOREA

 

As advanced comments, the korean government adopted various policies to reduce the  electric peak load in summer season. One is the installation of the district co-generation system which produces electric power by generator and produces hot water by wasted heat. The hot water is used for absorption chiller to make chilled water for cooling. Another is the development for commercial product of small capacity absorption chiller-heater for housekeeping. It is able to substitute the electric packaged air-conditioner which is occupied most portion of electric peak load.

 

1) Development of absorption chiller driven by low grade hot water for district cooling and heating. In the present, The hot water condition inlet 95 and outlet 80, is supplied to drive an absorption chiller for district cooling. But if the hot water is supplied at inlet 95 and outlet 55 in same pipe network, the cooling capacity is increased to 2.4 times with same hot water flow rate. For this purpose, The consortium comprised Century, Carrier, KDHC(Korea district heating corp.). and POSCO(Phohang steel corp.) and developed the pilot unit, 40 usRT, from 1998 to 1999 which is installed in the office building of KDHC and is operating for two years. The primary character of this system is that the absorption chiller has auxiliary absorber and auxiliary generator to be driven by low grade hot water to 50. And, the auxiliary solution heat exchanger and low temperature solution heat exchanger is added to enhance COP. Even though the achieved COP is 0.6 which is less than that of commercial product 95/80, 0.7 and The size is 1.3 times and the cooling tower is needed large capacity, hot water can be supplied to many unit and the cost of pipe network can be decreased. The following figure 2 and 3 shows the cycle and duhring diagram.

 

 

 

 

 

 

 

 

 

 

 

 

              Fig. 3. Cycle diagram of single effect-double lift absorption

 

 

 

 

2) Commercializing of household small absorbtion air-conditioner

To reduce the peak load of electricity, it is commercialized by century that is household small absorbtion air-conditioner, in stead of electrically driven package air conditioner.

Which, applied double effect absorbtion cycle, is introduced technological know-how from KO-GAS. The first commercialize product should be produced in 2002 of which capacity is 3 usRT(The sort of capacity should be extended to 1.5, 5, 7.5 usRT etc.).

 

 

This unit is adopted water cooled type for miniaturization and effectiveness, of which C.O.P for cooling & heating is 0.8. And also that is developed to multi type as three of indoor unit can be connected to one outdoor unit. The cooling cycle of the unit and duhring diagram are shown in Fig. 4 and 5.

 

 

 

 

 

    Fig. 4. Cooling cycle of small absorption air conditioner

Fig. 5. Duhring diagram of small absorption air conditioner.